Closed Circuit Cooling Towers | Baltimore Aircoil Company

By: Baltimore Aircoil  11-11-2011
Keywords: Technical Support, Energy Efficiency, Heat Transfer


Closed circuit cooling towers operate in a manner similar to open cooling towers, except that the heat load to be rejected is transferred from the process fluid (the fluid being cooled) to the ambient air through a heat exchange coil. The coil serves to isolate the process fluid from the outside air, keeping it clean and contaminate free in a closed loop. This creates two separate fluid circuits: (1) an external circuit, in which spray water circulates over the coil and mixes with the outside air, and (2) an internal circuit, in which the process fluid circulates inside the coil. During operation, heat is transferred from the internal circuit, through the coil to the spray water, and then to the atmosphere as a portion of the water evaporates.

Choosing the best closed circuit cooling tower

There is a wide variety of cooling tower concepts available on the market. It is for this reason that we recommend that you evaluate the different cooling tower configurations for your project. In order to select the best cooling tower for a specific application a number of factors should be considered. Listed below are a few questions which should be answered when making your choice.

About the application

  • What are the design conditions (flow rate, water in and out and entering wet bulb temperatures), which achieve the best energy efficiency for my process?
  • Are there acoustical limitations (sound power, sound pressure, day, night)?
  • What is the space available for the tower?
  • How can maintenance be conducted?
  • What is the condition of the make-up water?

About the supplier

  • What is the level of the manufacturer’s service and support?
  • Can the manufacturer demonstrate compliance with regulations and directives?
  • Who is my contact person for technical support and commercial assistance?

Compare the BAC Closed Circuit Cooling Towers

Addition of product accessories can improve standard product features, e.g. sound attenuation, premium efficiency motors, maintenance, and corrosion protection. Contact you BAC representative for more information.


BAC manufactures two types of closed circuit cooling towers: combined flow and counterflow.

Combined Flow

Combined flow is the use of both a heat exchange coil and fill for heat transfer in a closed circuit cooling tower. The addition of fill to the traditional closed circuit cooling tower design reduces evaporation in the coil section, reducing the potential for scaling and fouling. BAC’s combined flow closed circuit cooling towers utilize parallel flow of air and spray water over the coil, and crossflow air/water flow through the fill.

In parallel flow, air and water flow over the coil in the same direction. The process fluid travels from the bottom to the top of the coil, increasing efficiency by bringing the coldest spray water and air in contact with the process fluid at its coldest temperature.

In the fill of BAC’s combined flow closed circuit cooling towers, air and water interact in a crossflow configuration: water flows vertically down the fill as air flows horizontally across it.

Combined Flow: Parallel flow of air and water over the coil

Combined Flow: Crossflow configuration over the fill


In a counterflow closed circuit cooling tower design, the flow of the air is in the opposite direction of the spray water. In BAC’s counterflow closed circuit cooling towers, air travels vertically up through the unit while the spray water travels vertically down over the coil. The process fluid flows from top to bottom through the coil and is in thermal counterflow to the air.

Counterflow Configuration

Fan System

The flow of air through most factory assembled cooling towers is provided by one or more mechanically driven fans. The fan(s) may be axial or centrifugal, each type having its own distinct advantages. Axial fan units require approximately half the fan motor horsepower of comparably sized centrifugal fan units, offering significant energy savings.

Centrifugal fans

Axial fans

Centrifugal fan units are capable of overcoming reasonable amounts of external static pressure, making them suitable for both indoor and outdoor installations. Centrifugal fans are also inherently quieter than axial fans, although the difference is minimal and can often be overcome through the application of optional low sound fans and/or sound attenuation on axial fan units.

Induced Draft

The axial fans of induced draft equipment are mounted in the top deck of the unit, minimizing the impact of fan noise on nearby neighbors and providing maximum protection from fan icing with units operating in sub-freezing conditions. The use of corrosion resistant materials ensures long life and minimizes maintenance requirements for the air handling components.

Forced Draft

The fans are located on the air inlet face at the base of forced draft towers, facilitating easy access for routine maintenance and service. Additionally, the location of these components in the dry entering air stream extends component life by isolating them from the saturated discharge air.

Capacity Range

Product capacities are called out in terms of a flow rate at 30°C/25°C/21°C. This refers to the flow rate of water that the unit can cool from a 30°C entering water temperature to an 25°Cleaving water temperature at a 21°C entering wet-bulb temperature. BAC offers selection software to evaluate the performance of a closed circuit cooling tower at any conditions.

All capacities shown are for a single cell; multiple cell units can be applied to achieve larger capacities.

Maximum Entering Water Temperature

All BAC Closed Circuit Cooling Towers are capable of withstanding entering fluid temperatures as high as 82.2°C.

Advantages of Closed Circuit Cooling Towers

Open cooling towers expose process cooling water to the atmosphere, typically as part of a chiller system loop. Open towers use an efficient, simple, and economical design. All components in an open system must be compatible with the oxygen introduced via the cooling tower.

Chiller loop with open circuit cooling tower

Closed circuit cooling towers completely isolate the process cooling fluid from the atmosphere. This is accomplished by combining the heat rejection equipment with a heat exchanger in a closed circuit tower. A closed loop system protects the quality of the process fluid, reduces system maintenance, and provides operational flexibility at a slightly higher initial cost.

Chiller loop with closed circuit cooling tower

When deciding which system is best for an application, several factors should be considered.


If an application must produce full capacity throughout the year, maintaining a clean, reliable system loop is critical. Isolating the process fluid in a closed loop system prevents airborne contaminants from entering and fouling the system. Sustaining optimum performance in an open loop system will require regular maintenance to assure similar efficiency. High efficiency chillers and heat exchangers rely on clean process water to function properly and are significantly impacted by even small amounts of fouling.


The initial equipment cost of an open loop system will be less than a comparably sized closed loop system, since the open system does not include the intermediate heat exchanger component. However, the higher first cost of a closed loop system will be paid back during years of operation through the following savings:

  • Cleaner process fluid results in a cleaner internal surface area, and higher efficiency components in the system (e.g. chiller)
  • Reduced system maintenance costs
  • Reduced water treatment costs for evaporative equipment
  • Operating in ’free cooling’ mode during the winter to save energy consumption


Since the process fluid of a closed loop system is completely isolated from the environment, routine maintenance is only required on the heat rejection equipment itself. The need to shut down the system periodically to clean the heat exchanger is dramatically reduced, if not entirely eliminated. Providing clean process fluid to the system will extend the life of other components in the system (condenser bundles, compressors, etc.).

Water Treatment

Maintaining proper process fluid quality in a system may involve several steps, such as chemical treatment, filtration equipment and the addition of clean make-up water. A closed circuit cooling tower can provide the following advantages over an open cooling tower:

  • Lower volume of recirculating water to treat
  • Process loop requires minimal treatment
  • During periods of dry operation, the need for make-up water is eliminated

Operational Flexibility

Closed circuit towers allow for the following modes of operation not possible with open towers:

  • Free cooling operation without the need for an intermediate heat exchanger: Chiller turned off
  • Dry operation: Conserve water and treatment chemicals, prevent plume
  • Variable pumping: Closed condenser water loop allows for variable speed pumping to conserve energy

Closed Circuit Tower vs. Open Tower / Heat Exchanger

Sometimes, an open cooling tower is paired with a heat exchanger to capture some of the benefits of closed loop cooling. Choosing closed circuit cooling towers over this open tower/heat exchanger combination may still be a better choice for the following reasons:

  • Total cost: Addition of a heat exchanger (pump, piping, etc.) to the open tower loop brings the initial cost much closer to that of the closed circuit tower system
  • Single piece of equipment: Compact design of the closed circuit tower conserves space in a self-contained package, compared to multiple locations for the tower/heat exchanger arrangement
  • Maintenance: Narrow spacing in the heat exchanger (e.g. plate and frame) may trap solids introduced by the open tower, requiring frequent, time consuming cleaning to assure optimum performance
  • Dry operation: Open tower/heat exchanger system cannot be run dry in the winter

These guidelines provide some general information to help decide whether a closed circuit cooling tower is better suited for a particular application than an open tower, with or without a heat exchanger. For additional assistance with a project, please contact your local BAC Representative.

Chiller loop with open cooling tower/ heat exchanger combination

The Low Profile VFL Closed Circuit Cooling Towers deliver independently verified, fully rated thermal performance over a wide range of flow and temperature requirements. They can be installed indoors and are ideal for limited ceiling or enclosure heights. The Low Profile VFL design minimises sound levels and installation costs, provides year-round operating reliability, and simplifies maintenance requirements

The VXI Closed Circuit Cooling Towers with centrifugal fans delivers fully rated thermal performance over a wide range of flow and temperature requirements. The VXI can be installed indoors and can accommodate limited ceiling or enclosure heights. The VXI design minimises sound levels and installation costs, provides year round operating reliability, and simplifies maintenance requirements.

Keywords: Circuit Cooling, Closed Circuit Cooling, Closed Circuit Cooling Towers, Cooling Tower, Cooling Towers, Energy Efficiency, Heat Transfer, Technical Support,

Other products and services from Baltimore Aircoil


Products | Baltimore Aircoil Company

Closed circuit cooling towers operate in a manner similar to open cooling towers, except that the heat load to be rejected is transferred from the process fluid to the ambient air through a heat exchange coil. Evaporative condensers provide heat rejection for many types of systems, and the specific application will largely determine which BAC Evaporative Condenser is best suited for a project.


Open Circuit Cooling Towers | Baltimore Aircoil Company

The axial fans of induced draft equipment are mounted in the top deck of the unit, minimizing the impact of fan noise on nearby neighbors and providing maximum protection from fan icing with units operating in sub-freezing conditions.


VXT | Baltimore Aircoil Company

Materials of Construction - Various materials are available to meet the corrosion resistance, unit operating life, and budgetary requirements of any project. Indoor Installations: Centrifugal fans can overcome the static pressure imposed by external ductwork, allowing the VXT to be installed indoors. Support - All models mount directly on two parallel I-beams and ship complete with motors and drives factory-installed and aligned.


FXT | Baltimore Aircoil Company

Evaporative Cooling Equipment - Minimizes the energy consumption of the entire system because it provides lower condensing water temperatures. Easy lubrication – Fittings for extended lubrication lines are provided as standard on the exterior of the unit for bearing lubrication. High efficiency BACross® Fill, which provides maximum air/water contact time at low air pressure drops.


FXV | Baltimore Aircoil Company

The cleanable header tube bundle provides removable cover plates on the inlet and outlet header boxes to permit access to each serpentine tube circuit for solvent or air-pressure cleaning. The low sound levels generated by FXV Closed Circuit Cooling Towers make them suitable for installation in most environments. Tubes are all prime surface steel tubing formed into a serpentine shape and welded into an assembly.


VFL | Baltimore Aircoil Company

Low Profile Models– Motors and drives of low profile units are adjacent to the casing section to yield models suitable for use in height sensitive installations. Attenuation - For extremely sound sensitive applications, factory designed tested/rated sound attenuation is available for both the air intake and discharge.