Cable Installation & Hauling | Fibre Break

By: Fibre Break  11-11-2011
Keywords: Cables, Fibre, Fibre Optic

Installation methods for both wire cables and optical fibre cables are similar. Fibre cable can be pulled with much greater force than copper wire if you pull it correctly. Just remember these rules:

  • Do not pull on the fibres, pull on the strength members only! The cable manufacturer gives you the perfect solution to pulling the cables, they install special strength members, usually duPont Kevlar aramid yarn or a fibreglass rod to pull on. Use it! Any other method may put stress on the fibres and harm them. Most cables cannot be pulled by the jacket. Do not pull on the jacket unless it is specifically approved by the cable manufacturers and you use an approved cable grip.
  • Do not exceed the maximum pulling load rating. On long runs, use proper lubricants and make sure they are compatible with the cable jacket. On really long runs, pull from the middle out to both ends. If possible, use an automated puller with tension control or at least a breakaway pulling eye.
  • Do not exceed the cable bend radius. Fibre is stronger than steel when you pull it straight, but it breaks easily when bent too tightly. These will harm the fibres, maybe immediately, maybe not for a few years, but you will harm them and the cable must be removed and thrown away!
  • Do not twist the cable. Putting a twist in the cable can stress the fibres too. Always roll the cable off the spool instead of spinning it off the spool end. This will put a twist in the cable for every turn on the spool! If you are laying cable out for a long pull, use a “figure 8″ on the ground to prevent twisting (the figure 8 puts a half twist in on one side of the 8 and takes it out on the other, preventing twists.) And always use a swivel pulling eye because pulling tension will cause twisting forces on the cable.

Conduit and Innerduct: Outside plant cables are either installed in conduit or innerduct or direct buried, depending on the cable type. Building cables can be installed directly, but you might consider putting them inside plenum-rated innerduct. This innerduct is bright orange and will provide a good way to identify fibre optic cable and protect it from damage, generally a result of someone cutting it by mistake! The innerduct can speed installation and maybe even cut costs. It can be installed quickly by unskilled labour, then the fibre cable can be pulled through in seconds. You can even get the innerduct with pulling tape already installed.

Keywords: Cables, Fibre, Fibre Optic, Fibre Optic Cable, Optic Cable

Other products and services from Fibre Break


Design & Consultation | Fibre Break

Testing the Fibre Optic cable or network will be carried out by our own staff using either a multi-mode or single-mode Fibre Optic light source and power meters or our own multi-mode or single-mode OTDR test equipment. Our site based technical staff are also qualified in the installation and testing of complete Fibre Optic networks and are also fully trained to carry out splicing and jointing of Fibre Optic cables.


Splicing | Fibre Break

Mechanical Splices are alignment gadgets that hold the ends of two fibers together with some index matching gel or glue between them. Splicing is a “permanent” connection between two fibre cores, and is the preferred method for terminating. Field fusion splicing is usually done above ground in a truck or trailer set up for the purpose. Fusion Splices are made by “welding” the two fibers together by an electric arc.


Our Splicing And Testing Equipment

All splicing and testing equipment has calibration certification and certificates available on request. With our existing equipment we have successfully completed all our projects to the required standards. All our equipment is of optimum quality to ensure a high standard of workmanship and ease of work. Additional equipment would be purchase-dependent on the requirements of the project.